DocumentCode
2505543
Title
Effect of rack server population on temperatures in data centers
Author
Ghosh, Rajat ; Sundaralingam, Vikneshan ; Joshi, Yogendra
Author_Institution
G.W. Woodruff Sch. of Mech. Eng., Georgia Inst. of Technol., Atlanta, GA, USA
fYear
2012
fDate
May 30 2012-June 1 2012
Firstpage
30
Lastpage
37
Abstract
To reduce energy wastage during equipment upgrades that require changing the number of servers inside a rack, this paper investigates the effect of the server population of a rack on air temperatures in a data center facility. A rack-level containment system was implemented and air temperatures in cold and hot aisles with different numbers of servers were measured. A computational fluid dynamics (CFD)-based numerical model is used to study the air flow field. In addition, this paper includes the investigation of the effect of void locations on CPU temperatures. The study reveals that the server population inside a rack has a significant impact on air temperatures.
Keywords
computational fluid dynamics; computer centres; network servers; television transmitters; temperature; CFD-based numerical model; air temperatures; computational fluid dynamics; data centers; energy wastage reduction; rack server population; Computational fluid dynamics; Cooling; Monitoring; Servers; Temperature distribution; Temperature measurement; Tiles; Air Temperature; Containment; Data Centers; Energy Efficiency;
fLanguage
English
Publisher
ieee
Conference_Titel
Thermal and Thermomechanical Phenomena in Electronic Systems (ITherm), 2012 13th IEEE Intersociety Conference on
Conference_Location
San Diego, CA
ISSN
1087-9870
Print_ISBN
978-1-4244-9533-7
Electronic_ISBN
1087-9870
Type
conf
DOI
10.1109/ITHERM.2012.6231410
Filename
6231410
Link To Document