• DocumentCode
    2505543
  • Title

    Effect of rack server population on temperatures in data centers

  • Author

    Ghosh, Rajat ; Sundaralingam, Vikneshan ; Joshi, Yogendra

  • Author_Institution
    G.W. Woodruff Sch. of Mech. Eng., Georgia Inst. of Technol., Atlanta, GA, USA
  • fYear
    2012
  • fDate
    May 30 2012-June 1 2012
  • Firstpage
    30
  • Lastpage
    37
  • Abstract
    To reduce energy wastage during equipment upgrades that require changing the number of servers inside a rack, this paper investigates the effect of the server population of a rack on air temperatures in a data center facility. A rack-level containment system was implemented and air temperatures in cold and hot aisles with different numbers of servers were measured. A computational fluid dynamics (CFD)-based numerical model is used to study the air flow field. In addition, this paper includes the investigation of the effect of void locations on CPU temperatures. The study reveals that the server population inside a rack has a significant impact on air temperatures.
  • Keywords
    computational fluid dynamics; computer centres; network servers; television transmitters; temperature; CFD-based numerical model; air temperatures; computational fluid dynamics; data centers; energy wastage reduction; rack server population; Computational fluid dynamics; Cooling; Monitoring; Servers; Temperature distribution; Temperature measurement; Tiles; Air Temperature; Containment; Data Centers; Energy Efficiency;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Thermal and Thermomechanical Phenomena in Electronic Systems (ITherm), 2012 13th IEEE Intersociety Conference on
  • Conference_Location
    San Diego, CA
  • ISSN
    1087-9870
  • Print_ISBN
    978-1-4244-9533-7
  • Electronic_ISBN
    1087-9870
  • Type

    conf

  • DOI
    10.1109/ITHERM.2012.6231410
  • Filename
    6231410