Abstract :
The feasibility of a qualitative approach for detecting faults in an air-conditioning system is considered. The system considered is a multi-zone variable air volume air-handling unit, and the faults investigated include types which result in deterioration of operation as distinct from actual failure. The operating modes of the sequential controller for the central air-handling plant can be matched to a corresponding qualitative classification of steady-state temperatures. Observed mismatches indicate the presence of faults. First trials of the method in an air-conditioning test laboratory are reported
Keywords :
air conditioning; fault diagnosis; predictive control; temperature control; air-conditioning system; central air-handling unit; operation deterioration; qualitative classification; qualitative model-based fault detector; sequential controller; temperature control; Air conditioning; Fault diagnosis; Predictive control; Temperature control;