DocumentCode :
2510669
Title :
Calculation of the remaining lifetime of power transformers paper insulation
Author :
Gorgan, Bogdan ; Notingher, Petru V. ; Wetzer, Jos M. ; Verhaart, Harry F A ; Wouters, Peter A A F ; Van Schijndel, Arjan ; Tanasescu, Gabriel
Author_Institution :
Univ. Politeh. of Bucharest, Bucharest, Romania
fYear :
2012
fDate :
24-26 May 2012
Firstpage :
293
Lastpage :
300
Abstract :
This paper presents the remaining lifetime calculation of power transformers paper insulation and consequently of power transformers. The calculations are performed based on two models, which are related to the thermal degradation of the cellulose winding paper insulation: the common IEC loading guide and a paper degradation model. The paper insulation model´s prediction can be improved by involving data from furfural analysis. The remaining lifetime is extracted from the fault probability (reliability) of the paper insulation. The two models are brought together, to aid the asset manager in the decision making process. A probabilistic approach is used, which can be coupled to analysis in terms of risks, benefits, costs, and availability by the asset manager.
Keywords :
life testing; paper; power transformer insulation; transformer windings; IEC loading guide; cellulose winding paper insulation; fault probability; paper degradation model; paper insulation reliability; power transformers paper insulation; remaining lifetime calculation; thermal degradation; Degradation; Load modeling; Oil insulation; Power transformer insulation; Uncertainty;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Optimization of Electrical and Electronic Equipment (OPTIM), 2012 13th International Conference on
Conference_Location :
Brasov
ISSN :
1842-0133
Print_ISBN :
978-1-4673-1650-7
Electronic_ISBN :
1842-0133
Type :
conf
DOI :
10.1109/OPTIM.2012.6231792
Filename :
6231792
Link To Document :