Application of 10kV post-arrester in protection from induced-lightning in distribution network
Author
Tu Jun ; Zhou Wen-jun ; Yu Jian-hui
Author_Institution
Sch. of Electr. Eng., Wuhan Univ., Wuhan, China
fYear
2010
fDate
12-16 April 2010
Firstpage
1547
Lastpage
1549
Abstract
The tolerance level of the induced-lightning and the trip-out rate of applying different lightning protection measures on 10 kV lines are gotten by emulating in ATPDraw and calculating. Though researching the destiny of the installation of post-arrester, the conclusion is reached that it´s no obvious effect on reducing lightning trip-out rate to place post-arresters at intervals. Only if arresters are installed continuously, the lightning trip-out rate will be reduced obviously. But it is not economical to install arresters continuously on the whole lines. So more-thunderstorm regions should be selected out to install arresters continuously.
Keywords
arresters; lightning protection; power distribution protection; ATPDraw; distribution network; induced-lightning protection; lightning trip-out rate; post-arrester; voltage 10 kV; Arresters; Electric shock; Inductance; Insulation; Lightning protection; Poles and towers; Power system reliability; Switches; Voltage control; Wires;