Title :
Tests on electromagnetic environment of ultra HVDC transmission lines in high altitude region
Author :
Yu, Zhanqing ; Zeng, Rong ; Li, Min ; Li, Ruihai ; Liu, Lei ; Zhang, Bo ; Zhang, Zheng ; Zhang, Huaying
Author_Institution :
Dept. of Electr. Eng., Tsinghua Univ., Beijing, China
Abstract :
The Ultra High Voltage DC power transmission technique is developed quickly in China but used barely in the world. Corona phenomenon in high altitude region is more serious, and corresponding electromagnetic environment is more severe as well. A UHVDC test lines are completed for tests in Kunming, China, with an altitude of 2100 m. An automotive electromagnetic environment testing system was installed under the line. Measurement of electromagnetic environment was carried out. Radio interference, audible noise, resultant electric field and ion current density at ground level were measured at different voltage from ±800kV to ±1000kV, and atmosphere conditions including sunny, rainy and cloudy weather. The measured result show some difference with those acquired at sea level and is significant for further studies of corona mechanism under high altitude condition. Measured results were compared with the calculated results.
Keywords :
HVDC power transmission; electromagnetic interference; environmental testing; power transmission lines; China; UHVDC power transmission technique; audible noise; automotive electromagnetic environment testing; high altitude region; radio interference; ultra high voltage; Atmospheric measurements; Automotive engineering; Corona; Electromagnetic interference; Electromagnetic measurements; HVDC transmission; Power transmission; Sea measurements; System testing; Voltage;
Conference_Titel :
Electromagnetic Compatibility (APEMC), 2010 Asia-Pacific Symposium on
Conference_Location :
Beijing
Print_ISBN :
978-1-4244-5621-5
DOI :
10.1109/APEMC.2010.5475639