Title :
Experience with an on-line monitoring system for 400 kV XLPE cables
Author :
Henningsen, C.G. ; Polster, K. ; Fruth, Bernhard A. ; Gross, Detlev W.
Author_Institution :
BEWAG, Berlin, Germany
Abstract :
The use of high voltage cables is today recommended and sometimes mandatory in order to avoid environmental concerns of the public, especially when the power system crosses areas of dense population. The reunion of the former GDR with the Federal Republic of Germany has stimulated the interest in this settlement especially for the city of Berlin, where the increase of energy demand requires the use of innovative solutions. The paper reports the activities that BEWAG, the electrical utility of Berlin, performs in order to investigate the feasibility of setting up an urban bulk power connection using 400 kV XLPE cables. During a first accelerated voltage endurance test (at CESI in Milan/Italy) on cables and accessories of six major European manufacturers several failures in joints and SF6 terminations were encountered. Therefore the cable links for the actual second testing period were additionally equipped with partial discharge sensors for an insulation monitoring system. Sensors of this type will in the future be integrated into the cable accessories to improve after laying quality control. It is thought that this partial discharge test will replace high voltage DC-tests which were found unsuitable for the 400 kV XLPE cable technology
Keywords :
XLPE insulation; cable jointing; charge measurement; computerised monitoring; insulation testing; life testing; partial discharges; power cable insulation; power cable testing; power cables; 400 kV; BEWAG; Berlin; Germany; XLPE cables; accelerated voltage endurance test; cable joints; cable terminations; electrical utility; insulation monitoring system; on-line monitoring system; partial discharge sensors; quality control; urban bulk power connection; Cables; Cities and towns; Insulation testing; Life estimation; Manufacturing; Monitoring; Partial discharges; Power systems; System testing; Voltage;
Conference_Titel :
Transmission and Distribution Conference, 1996. Proceedings., 1996 IEEE
Conference_Location :
Los Angeles, CA
Print_ISBN :
0-7803-3522-8
DOI :
10.1109/TDC.1996.547564