Abstract
To develop the composite insulator termination for EHV XLPE Cable, especially for those used for contamination conditions, it is necessary to evaluate the contamination performance of composite insulators. This article presents the results of artificial contamination test on the cylindrical model made of FRP tube covered with silicone rubber, and also introduces the relation between methods of making contamination samples and the equivalent salt deposit density (ESDD) levels on the surface of the samples. Comparing with salt (NaCl), a mixture of several contamination deposits was also used to evaluate the contamination performance of the samples. Artificial contamination tests were performed in a clean fog room. Several contaminated silicone rubber cylindrical samples with different diameters were tested. AC flashover voltage was measured by changing the ESDD level
Keywords
composite insulators; flashover; insulator contamination; insulator testing; silicone rubber insulators; AC flashover voltage; EHV XLPE cable; FRP tube; artificial contamination test; clean fog; composite insulator termination; cylindrical model; equivalent salt deposit density; silicone rubber; Cable insulation; Fiber reinforced plastics; Flashover; Performance evaluation; Pollution measurement; Rubber; Surface cleaning; Surface contamination; Testing; Voltage measurement;
fLanguage
English
Publisher
ieee
Conference_Titel
Properties and Applications of Dielectric Materials, 2000. Proceedings of the 6th International Conference on
Conference_Location
Xi´an
Print_ISBN
0-7803-5459-1
Type
conf
DOI
10.1109/ICPADM.2000.875684
Filename
875684
Link To Document