DocumentCode :
2522008
Title :
A study of the correlation of leakage current, humidity and temperature of 25 kV insulators in urban and rural areas
Author :
Meyer, L.H. ; Oliboni, C.R.P. ; Graziano, G.C. ; Mustafa, T.I.A.H. ; Almaguer, H.A.D. ; Molina, F.H. ; Cassel, G.
Author_Institution :
Dept. of Elec. Eng., Univ. of Blumenau, Blumenau, Brazil
fYear :
2011
fDate :
16-19 Oct. 2011
Firstpage :
398
Lastpage :
402
Abstract :
A leakage current monitor was developed to measure and register the leakage current on the surface of ceramic line post insulators. Along with the leakage current, the ambient relative humidity and temperature were also measured and registered in insulators installed in urban and rural areas. The paper shows the results of these variables measurement and a correlation study among them. Main conclusions are that the leakage current is strongly dependent on ambient humidity. In polluted insulators the leakage current presents rather a random behavior, with lower dependency on the humidity.
Keywords :
ceramic insulators; electric current measurement; humidity measurement; leakage currents; ambient relative humidity; ambient relative temperature; ceramic line post insulators; humidity insulators; leakage current correlation; leakage current measurement; leakage current monitor; polluted insulators; rural areas; temperature insulators; urban areas; voltage 25 kV; Correlation; Humidity; Insulators; Leakage current; Monitoring; Temperature measurement; Temperature sensors;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Electrical Insulation and Dielectric Phenomena (CEIDP), 2011 Annual Report Conference on
Conference_Location :
Cancun
ISSN :
0084-9162
Print_ISBN :
978-1-4577-0985-2
Type :
conf
DOI :
10.1109/CEIDP.2011.6232679
Filename :
6232679
Link To Document :
بازگشت