UHF detection of PD in power transformers: The influence of disturbances
Author
Cavallini, Andrea ; Ramos, Carlos Gustavo Azcarraga ; Montanari, Gian Carlo ; Saad, Hani ; Tozzi, Marco
Author_Institution
Dipt. di Ing. Elettr., Univ. di Bologna, Bologna, Italy
fYear
2011
fDate
16-19 Oct. 2011
Firstpage
436
Lastpage
439
Abstract
Ultra-high frequency partial discharge sensors are often deemed to be immune to disturbance, i.e., signals generated by partial discharge sources outside the transformer itself. In this paper, the above claim is investigated resorting to both computer simulations and experimental tests. The results indicate that corona from power lines in proximity of a transformer, or surface discharges on the surface of bushings can provide signals that are comparable with those generated by PD sources. These findings suggest that care must be taken when evaluating data coming from this type of sensors, as false alarms can be obtained.
Keywords
UHF detectors; partial discharges; power transformers; UHF detection; computer simulations; corona; disturbance influence; experimental; power lines; power transformers; surface discharges; transformer proximity; ultra-high frequency partial discharge sensors; Conductors; Corona; Insulators; Partial discharges; Power transformers; Sensors; Surface discharges;