DocumentCode
2522812
Title
Parameters affecting the static electrification of aged transformer oils
Author
N´Cho, J.S. ; Fofana, I. ; Beroual, A.
Author_Institution
AMPERE, Ecole Centrale de Lyon, Ecully, France
fYear
2011
fDate
16-19 Oct. 2011
Firstpage
571
Lastpage
574
Abstract
In this contribution, experimental investigations onto the factors affecting the static electrification of aged transformer oils are undertaken. The effect of aging byproducts (as assessed by Dissolved Decay products, Turbidity, Interfacial Tension and Acid number) of the oil on the streaming current is reported. The results indicate that the electrification currents generally increase with aging by-products of oil. The sign, the amplitude and the time constant of the electrification currents are also affected. The influence of each “impurity” is emphasized and discussed.
Keywords
transformer oil; acid number; aged transformer oil static electrification; aging byproduct effect; dissolved decay products; electrification currents; interfacial tension; oil aging by-products; Aging; Current measurement; Insulation; Leakage current; Oils; Power transformer insulation;
fLanguage
English
Publisher
ieee
Conference_Titel
Electrical Insulation and Dielectric Phenomena (CEIDP), 2011 Annual Report Conference on
Conference_Location
Cancun
ISSN
0084-9162
Print_ISBN
978-1-4577-0985-2
Type
conf
DOI
10.1109/CEIDP.2011.6232721
Filename
6232721
Link To Document