    Adding life and safety to existing substations

  • Author

    Metzdorf, M.A. ; Martin, Michael C. ; Webb, J.C.

  • Author_Institution
    LyondellBasell, Channelview, TX, USA
  • fYear
    2012
  • fDate
    24-26 Sept. 2012
  • Firstpage
    1
  • Lastpage
    9
  • Abstract
    This paper will discuss a set of projects in a large US chemical manufacturing facility which lowered the arc flash incident energy at several 480-volt switchgear lineups and extended the life of the equipment through the installation of retrofit circuit breakers. After the arc flash hazard study was completed at the facility, it was found that many 480-volt, 1000 kVA substation switchgear lineups had incident energy levels well above safe working conditions. Additionally, with major unit outages approaching, it was desired to find a cost-effectively way to extend the life of the existing, 35-year old equipment. Through analysis and field trials it was determined that the upstream fuses could be replaced with a lower rating and significantly reduce the arc flash incident energy to within acceptable levels. Additionally, a retrofit circuit breaker was found which did not require any physical modifications to the switchgear and provided a new breaker in place of the old equipment. The advanced features of the new breaker trip unit allows personnel to activate an alternate trip setting which lowers the downstream arc flash incident energy on the motor control centers to minimal levels allowing less protective equipment when performing common energized tasks. Finally, with the addition of electrical control, personnel are able to operate the new breakers remotely outside of the arc flash hazard boundary.
  • Keywords
    arcs (electric); circuit breakers; safety; substations; US chemical manufacturing facility; arc flash hazard; arc flash hazard boundary; arc flash incident energy; electrical control; motor control centers; personnel; retrofit circuit breakers; safety; substation switchgear lineups; switchgear lineups; voltage 480 V; Arc Flash Reduction; Circuit Breaker Replacement; Low Voltage Circuit Breakers; Substation Life Extension;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Petroleum and Chemical Industry Technical Conference (PCIC), 2012 Record of Conference Papers Industry Applications Society 59th Annual IEEE
  • Conference_Location
    Chicago, IL
  • ISSN
    0090-3507
  • Print_ISBN
    978-1-4673-0924-0
  • Type

    conf

  • DOI
    10.1109/PCICON.2012.6549664
  • Filename
    6549664