Analysis of transformer inrush current and comparison of harmonic restraint methods in transformer protection
Author :
Hamilton, R.
Author_Institution :
Basler Electr. Co., Highland, IL, USA
fYear :
2012
fDate :
24-26 Sept. 2012
Firstpage :
1
Lastpage :
10
Abstract :
Security is of concern in differential protection during transformer energization. Inrush current occurs mostly in only one side of the transformer and could cause a false differential trip. A common restraint method is to use the second harmonic information in the inrush current to secure differential protection when energizing transformers.
Keywords :
power system harmonics; power transformer protection; common restraint method; differential protection; false differential trip; harmonic restraint methods; second harmonic information; transformer energization; transformer inrush current; transformer protection;