DocumentCode :
2525831
Title :
An improved interharmonic grouping scheme based on IEC 61000-4-7
Author :
Hui, Jin ; Yang, Honggeng ; Xu, Wilsun ; Liu, Yamei
Author_Institution :
Coll. of Electr. Eng. & Inf. Technol., Sichuan Univ., Chengdu, China
fYear :
2012
fDate :
17-20 June 2012
Firstpage :
178
Lastpage :
181
Abstract :
The interharmonic group concept adopted by the IEC 61000-4-7 is very useful for addressing the need to monitor interharmonics in power systems. This paper shows that grouping spectral bins into interharmonics and harmonic components of 5Hz resolution could yield misleading information for cases where an interharmonic component´s frequency is very close to a harmonic frequency. Since interharmonics in such cases can cause more severe waveform modulation, the interharmonic grouping scheme needs to be improved. A signal processing method that can separate interharmonic and harmonic components in close proximity is, therefore, proposed in this paper to address this need. Field data analysis showed that the proposed method was able to extract interharmonic and harmonic components correctly.
Keywords :
data analysis; power system harmonics; power system measurement; IEC 61000-4-7; field data analysis; frequency 5 Hz; harmonic component frequency; harmonic components; improved interharmonic grouping scheme; interharmonic component frequency; power system interharmonic monitoring; waveform modulation; Equations; DFT; Harmonic analysis; interharmonics; spectral leakage;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Harmonics and Quality of Power (ICHQP), 2012 IEEE 15th International Conference on
Conference_Location :
Hong Kong
ISSN :
1540-6008
Print_ISBN :
978-1-4673-1944-7
Type :
conf
DOI :
10.1109/ICHQP.2012.6381213
Filename :
6381213
Link To Document :
بازگشت