DocumentCode
2525962
Title
Study of PD detection and location by means of acoustic measurements transformer
Author
Xiaoyun, Hu ; Yifeng, Li ; Yi, Lu
Author_Institution
Southeast Univ., Nanjing, China
Volume
2
fYear
2000
fDate
2000
Firstpage
753
Abstract
This paper applies a pattern recognition method for localisation of the PD site in the oil-filled transformer by acoustic measurements. By dividing the transformer into N numbers of 20×20×20 mm 3 sub-modules, the PD site is localised by comparing the spatial distances of each sub-module to the acoustic sensors. The numerical cases indicate that the proposed method is general and practical while avoiding some drawbacks in current algorithms. Moreover, the method improves the accuracy of localisation substantially when compared with the conventional localization method
Keywords
acoustic transducers; insulation testing; partial discharge measurement; pattern recognition; power transformer insulation; power transformer testing; transformer oil; acoustic measurements; acoustic sensors; oil-filled transformer; partial discharge localisation; pattern recognition; Acoustic measurements; Acoustic propagation; Acoustic sensors; Acoustic signal detection; Acoustic waves; Mathematical model; Oil insulation; Partial discharges; Pattern recognition; Petroleum;
fLanguage
English
Publisher
ieee
Conference_Titel
Properties and Applications of Dielectric Materials, 2000. Proceedings of the 6th International Conference on
Conference_Location
Xi´an
Print_ISBN
0-7803-5459-1
Type
conf
DOI
10.1109/ICPADM.2000.876339
Filename
876339
Link To Document