DocumentCode
2526821
Title
Discussion on the relation between residual breakdown voltage and nondestructive parameters of stator insulation in generator
Author
Jia, Zhidong ; Jiang, Xiongwei ; Xie, Hengkun ; Wang, Ruijun
Author_Institution
State Key Lab. of Electr. Insulation for Power Equipment, Xi´´an Jiaotong Univ., China
Volume
2
fYear
2000
fDate
21-26 June 2000
Firstpage
970
Abstract
A long-term accelerated aging test of generator stator insulation in the laboratory was conducted. Nondestructive parameters, such as dissipation factor (tan /spl delta/), capacitance (C) and the voltage (U/sub 12/) at which the current increases abruptly, were measured in the period of the aging test. The breakdown test was performed to determine residual breakdown voltage (BDV). The correlation coefficients between BDV and nondestructive parameters were compared. The most effective parameter to describe the aging condition of the stator insulation was U/sub 12/. The relationship between BDV and nondestructive parameters was also analyzed theoretically.
Keywords
AC generators; ageing; capacitance; composite insulating materials; dielectric losses; electric breakdown; insulation testing; life testing; machine testing; nondestructive testing; stators; aging condition; capacitance; correlation coefficients; dissipation factor; epoxy mica insulation; generator stator insulation; long-term accelerated aging test; multi-stress aging; nondestructive parameters; residual breakdown voltage; Aging; Dielectrics and electrical insulation; Electrodes; Insulation testing; Laboratories; Low voltage; Nondestructive testing; Power generation; Stators; Thermal stresses;
fLanguage
English
Publisher
ieee
Conference_Titel
Properties and Applications of Dielectric Materials, 2000. Proceedings of the 6th International Conference on
Conference_Location
Xi´an, China
Print_ISBN
0-7803-5459-1
Type
conf
DOI
10.1109/ICPADM.2000.876392
Filename
876392
Link To Document