DocumentCode :
2530026
Title :
Transient analysis of the 161-kV Taiwan- PengHu submarine power cable system
Author :
Ho, Ping-Heng ; Wu, Chi-Jui
Author_Institution :
Dept. of Electr. Eng., Nat. Taiwan Univ. of Sci. & Technol., Taipei
fYear :
2008
fDate :
20-24 July 2008
Firstpage :
1
Lastpage :
8
Abstract :
The 58.9-km, 161-kV Taiwan PengHu submarine power cable system (T-P-Cable), the first submarine project of the Taiwan Power Company (Taipower) in this level, will be commercially operated in 2012. It is important to analyze the transient behaviors before operation. It is necessary to find the operation strategy to deal with the transients in advance. The EMTP-ATP was used in this paper to analyze (1) the switched over voltage (SOV) in normal operation, (2) the slow front transients (SFT) voltage in fault contingency, (3) the transient inrush current (TIC) in energizing of the no-load transformers and shunt reactors, and (4) the transient recover voltage (TRV) in de-energizing the shunt reactors. The appropriate set of the surge protective device (SPD) to avoid the SOV and SFT has also been investigated. The results show that there is no TIC in energizing the no-load transformers and shunt reactors. The TRV across the current breaker (CB) contactors is higher than the system TRV when the shunt reactors are de-energized without using SPD. There is no re-strike on the CB contactors. The results of this study provide tremendous prior operation experience and advice for the Taipower.
Keywords :
submarine cables; surge protection; transient response; EMTP-ATP; Taipower; Taiwan Power Company; Taiwan-PengHu submarine power cable system; current breaker contactors; fault contingency; no-load transformers; shunt reactors; slow front transients voltage; surge protective device; switched over voltage; transient analysis; transient inrush current; transient recover voltage; voltage 161 kV; Contactors; Inductors; Power cables; Shunt (electrical); Surge Protective Devices - c62; Surge protection; Transformers; Transient analysis; Underwater vehicles; Voltage control; EMTP; Power System Transients; Slow Front Transients; Submarine Power Cable; Switched Over Voltage; Transient Inrush Current; Transient Recovery Voltage;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Power and Energy Society General Meeting - Conversion and Delivery of Electrical Energy in the 21st Century, 2008 IEEE
Conference_Location :
Pittsburgh, PA
ISSN :
1932-5517
Print_ISBN :
978-1-4244-1905-0
Electronic_ISBN :
1932-5517
Type :
conf
DOI :
10.1109/PES.2008.4596007