Abstract
Distributed Generations (DGs) much have obtained attentions to be used in practical systems while protection issues against islanding phenomenon needs to be taken into the account. This paper introduces also analysis controlling feedback in order to construct reference current in constant current islanding detection to find out islanding phenomenon for inverter-based DGs. In this paper, d-axis reference current has been functionalized respecting PCC voltage and then designed in order to highly mitigate none detection zone (NDZ). At first the validity of the proposed strategy mathematically was analyzed from power and stability point of view, then under real power system situation (i.e. multiple DG case, load switching, voltage sags and swells). The simulation results were carried out through MATLAB/Simulink environment proved performance of this easy-to-implement islanding detection method.
Keywords
distributed power generation; power distribution faults; power system stability; MATLAB; NDZ; PCC voltage; Simulink; constant current islanding detection; d-axis reference current; none detection zone; stability analysis; MATLAB; Performance evaluation; Radio frequency; Switches; Voltage fluctuations; Constant current method; inverter-based DGs; islanding phenomenon; none detection zone;
fLanguage
English
Publisher
ieee
Conference_Titel
Power Electronics, Drives Systems & Technologies Conference (PEDSTC), 2015 6th
Conference_Location
Tehran
Print_ISBN
978-1-4799-7652-2
Type
conf
DOI
10.1109/PEDSTC.2015.7093321
Filename
7093321
Link To Document