• DocumentCode
    2530646
  • Title

    Improved constant current islanding detection with regardless NDZ and its stability analysis

  • Author

    Dehghani, A. ; Geramirad, H. ; Hosseinian, S.H.

  • Author_Institution
    Electr. Eng. Dept., Amirkabir Univ. of Technol., Tehran, Iran
  • fYear
    2015
  • fDate
    3-4 Feb. 2015
  • Firstpage
    474
  • Lastpage
    479
  • Abstract
    Distributed Generations (DGs) much have obtained attentions to be used in practical systems while protection issues against islanding phenomenon needs to be taken into the account. This paper introduces also analysis controlling feedback in order to construct reference current in constant current islanding detection to find out islanding phenomenon for inverter-based DGs. In this paper, d-axis reference current has been functionalized respecting PCC voltage and then designed in order to highly mitigate none detection zone (NDZ). At first the validity of the proposed strategy mathematically was analyzed from power and stability point of view, then under real power system situation (i.e. multiple DG case, load switching, voltage sags and swells). The simulation results were carried out through MATLAB/Simulink environment proved performance of this easy-to-implement islanding detection method.
  • Keywords
    distributed power generation; power distribution faults; power system stability; MATLAB; NDZ; PCC voltage; Simulink; constant current islanding detection; d-axis reference current; none detection zone; stability analysis; MATLAB; Performance evaluation; Radio frequency; Switches; Voltage fluctuations; Constant current method; inverter-based DGs; islanding phenomenon; none detection zone;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Power Electronics, Drives Systems & Technologies Conference (PEDSTC), 2015 6th
  • Conference_Location
    Tehran
  • Print_ISBN
    978-1-4799-7652-2
  • Type

    conf

  • DOI
    10.1109/PEDSTC.2015.7093321
  • Filename
    7093321