Influence of fault current limiter on isolated operation of customer system with synchronous generator
Author :
Iioka, Disuke ; Yokomizu, Y. ; Matsumura, Takeshi
Author_Institution :
Dept. of Electr. Eng. & Comput. Sci., Nagoya Univ., Nagoya
fYear :
2008
fDate :
20-24 July 2008
Firstpage :
1
Lastpage :
5
Abstract :
Influences of a fault current limiter (FCL) on an isolated operation of a customer system with a synchronous generator are discussed for a fault occurrence. The customer system is supposed to be interconnected to a medium voltage feeder of the utility system through the FCL to reduce the fault current from the customer generator. When the fault occurs at the feeder, the customer system has to be disconnected from the utility system to keep the power supply in the customer system. If the separation of the customer system from the utility one is too late (in other words, if the continuous interconnecting time period after the fault occurrence is too long), the customer generator could not make the shift to the isolated operation mode because of the inadequate balance between the generator and loads. The allowable interconnecting time period to make the successful shift to the isolated operation mode is simulated by using PSCAD/EMTDC. It was found that a resistive type fault current limiter (R-type FCL) does not improve the allowable interconnecting time period since the consumption power in the R-type FCL causes the generator to decelerate. However, it was shown that the allowable interconnecting time period increases owing to the application of inductive type fault current limiter (L-type FCL). This is because the active power of load is nearly equal to the generator output. The influence of reverse power flow out of customer system on the isolated operation was also clarified.
Keywords :
fault current limiters; power system CAD; synchronous generators; EMTDC; PSCAD; continuous interconnecting time period; customer system; fault occurrence; medium voltage feeder; resistive type fault current limiter; reverse power flow; synchronous generator; utility system; EMTDC; Fault current limiters; Fault currents; Load flow; Medium voltage; PSCAD; Power generation; Power supplies; Power system interconnection; Synchronous generators; Critical Disconnection Time; Distributed Generator; Fault Current Limiter; Isolated Operation;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Power and Energy Society General Meeting - Conversion and Delivery of Electrical Energy in the 21st Century, 2008 IEEE
Conference_Location :
Pittsburgh, PA
ISSN :
1932-5517
Print_ISBN :
978-1-4244-1905-0
Electronic_ISBN :
1932-5517
Type :
conf
DOI :
10.1109/PES.2008.4596193
Filename :
4596193
Link To Document :
بازگشت