DocumentCode :
2535683
Title :
Study of rapid thermal evaluation for form-wound winding insulation systems
Author :
Weixian Li ; Jingliang Li
Author_Institution :
Shanghai Electr. Apparatus Res. Inst.
fYear :
1988
fDate :
12-16 Sep 1988
Firstpage :
438
Abstract :
It is shown that the results of one high-temperature point from the conventional thermal aging test and the slope obtained by instrument analysis can be used to determine the thermal life line of form-wound winding insulation systems, thus leading to the determination of the temperature index and the thermal life. The conventional aging test is carried on according to IEC Pub. 611 and IEEE Std. 275. The instrument analysis makes use of two methods: gas-chromatography and thermogravimetry analysis. Six form-wound winding insulation systems have been evaluated. The results of two rapid thermal aging test methods agree fairly well with the conventional aging methods. It is noted that the proposed technique is more cost- and time-effective than the conventional thermal aging test
Keywords :
ageing; composite insulating materials; insulation testing; life testing; machine insulation; materials testing; organic insulating materials; cost effective; form-wound winding insulation systems; gas-chromatography; high-temperature point; instrument analysis; rapid thermal aging test methods; rapid thermal evaluation; slope; temperature index evaluation; thermal aging test; thermal life evaluation; thermal life line; thermogravimetry analysis; time-effective; Aging; Equations; Gas insulation; Instruments; Insulation testing; Life testing; Materials testing; System testing; Temperature; Thermal degradation;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Properties and Applications of Dielectric Materials, 1988. Proceedings., Second International Conference on Properties and Applications of
Conference_Location :
Beijing
Type :
conf
DOI :
10.1109/ICPADM.1988.38428
Filename :
38428
Link To Document :