Title :
Islanding operation of inverter based Distributed Generation with static load models
Author :
Zeineldin, H.H. ; Kirtley, J.L., Jr.
Author_Institution :
Masdar Inst. of Sci. & Technol., Abu Dhabi
Abstract :
Distributed generation (DG) islanding is usually analyzed and tested using RLC loads. In this paper, the performance of inverter based DG during an islanding condition is analyzed taking into account the different load models (constant impedance, constant power and constant current). The DG is operated as constant power source operating at unity power factor. The effect of voltage and frequency dependence of system load on performance of an islanded system fragment is also examined. Based on computer simulation, the active powerpsilas load dependence parameters have the most significant effect. It is shown that the ldquonon-detection zonerdquo is affected by both load voltage and frequency dependence.
Keywords :
distributed power generation; invertors; power factor; active powers load dependence parameters; computer simulation; constant current; constant impedance; constant power source operation; distributed generation islanding; frequency dependence; inverter based distributed generation; load voltage; static load models; unity power factor; Distributed control; Frequency dependence; Impedance; Inverters; Load modeling; Performance analysis; Power system modeling; Reactive power; Testing; Voltage; Distributed Generation; Inverter; Islanding; Over/Under Frequency; Over/Under Voltage; Static Load Models;
Conference_Titel :
Power and Energy Society General Meeting - Conversion and Delivery of Electrical Energy in the 21st Century, 2008 IEEE
Conference_Location :
Pittsburgh, PA
Print_ISBN :
978-1-4244-1905-0
Electronic_ISBN :
1932-5517
DOI :
10.1109/PES.2008.4596337