Abstract
This paper investigates on distance relay characteristic for hybrid line; an overhead transmission line combined with a cable. Introducing ABCD parameter approach to sequence network the apparent impedance equation is derived that includes line capacitance. For a 400 kV hybrid transmission system results show that shunt capacitance has significant effect on settings for adaptive relaying. It is observed that the trip characteristic for hybrid line is unique. An adaptive setting method using local information is proposed and tested using simulated data obtained through EMTDC-PSCAD.
Keywords
hybrid power systems; power cables; power overhead lines; power transmission protection; relays; ABCD parameter approach; EMTDC- PSCAD; adaptive distance relay setting; apparent impedance equation; hybrid power transmission network; local information; overhead transmission line; power cable; sequence network; shunt capacitance; trip characteristic; voltage 400 kV; Capacitance; Impedance; Power cables; Protective relaying; Resistance; Adaptive relaying; Apparent impedance; Distance relay; Hybrid line; Line Protection; Trip Characteristic;
fLanguage
English
Publisher
ieee
Conference_Titel
Innovative Smart Grid Technologies Conference Europe (ISGT-Europe), 2014 IEEE PES
Conference_Location
Istanbul
Type
conf
DOI
10.1109/ISGTEurope.2014.7028823
Filename
7028823
Link To Document