Abstract :
This paper discusses the distance relay ideal tripping characteristic in the presence of static synchronous series compensator (SSSC), one of the series connected flexible alternating current transmission system (FACTS) devices, on the next line, in the case of inter phase, phase to phase and three phase, faults. Especial attention is paid to the over-reaching problem. This is done by presenting the measured impedance at the relaying point in the presence of SSSC at the near end of the next line. The measured impedance at relaying point is greatly influenced in the presence of SSSC on the protected line or even on the near end of the next line. The measured impedance at relating point depends on many factors including the power system structural conditions, pre-fault loading, fault resistance, and SSSC structural and controlling parameters.
Keywords :
electric impedance measurement; flexible AC transmission systems; power system relaying; power transmission faults; power transmission lines; power transmission protection; static VAr compensators; FACTS devices; SSSC; distance relay ideal tripping characteristics; flexible alternating current transmission system devices; impedance measurement; inter phase faults; static synchronous series compensator; transmission lines; Control systems; Electrical resistance measurement; Flexible AC transmission systems; Impedance measurement; Power measurement; Power system faults; Power system measurements; Power system protection; Power system relaying; Protective relaying;
Conference_Titel :
Electrical and Computer Engineering, 2008. ICECE 2008. International Conference on
Conference_Location :
Dhaka
Print_ISBN :
978-1-4244-2014-8
Electronic_ISBN :
978-1-4244-2015-5
DOI :
10.1109/ICECE.2008.4769228