    Measurement of tgδ and C of single-phase electrical apparatus with capacitive insulation under operating voltage

  • Author

    Zhu, Guangxu ; Wang, Jiacheng

  • Author_Institution
    Guandong Gen. Power Co.
  • fYear
    1988
  • fDate
    12-16 Sep 1988
  • Firstpage
    701
  • Abstract
    The authors describe a method of measuring tgδ (loss tangent) and C (capacitance) of a single-phase apparatus with capacitive insulation by using an ordinary Schering bridge which takes the secondary voltage of a same-phase power transformer as the voltage of the standard arm and suppresses interference. Examples are given to illustrate how to analyze the results of measurement. The proposed method is safe and reliable, since testers need not come into contact with the high-voltage side of the apparatus, and a series of safety measures are taken. Because errors and interference are eliminated, the measuring data is stable and the accuracy high
  • Keywords
    capacitance measurement; dielectric loss measurement; high-voltage techniques; insulation testing; loss-angle measurement; measurement errors; power apparatus; HV apparatus; Schering bridge; capacitance measurement; capacitive insulation; error elimination; high-voltage; interference suppression; loss tangent measurement; safety measures; single-phase electrical apparatus; Bridge circuits; Capacitance measurement; Interference suppression; Loss measurement; Measurement standards; Power measurement; Power transformer insulation; Power transformers; Safety; Testing;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Properties and Applications of Dielectric Materials, 1988. Proceedings., Second International Conference on Properties and Applications of
  • Conference_Location
    Beijing
  • Type

    conf

  • DOI
    10.1109/ICPADM.1988.38496
  • Filename
    38496