DocumentCode
2542186
Title
Furan measurement in transformer oil by UV-Vis spectral response using Fuzzy Logic
Author
Lai, Sin Pin ; Abu-Siada, Ahmed ; Islam, Syed
Author_Institution
Dept. of Electr. & Comput. Eng., Curtin Univ. of Technol., Perth, WA, Australia
fYear
2008
fDate
20-22 Dec. 2008
Firstpage
716
Lastpage
720
Abstract
Furan derivatives (2-acetyl furan, 2-furfural, 5-methyl-2-furfural, 5-hydroxymethyl 2-furfural, and 2-furfurylalcohol) presence in transformer oil are the key indicators of the solid dielectric degradation. In recent technology, such deterioration is measured according to ASTM D 5837 standard. However, the method requires very expensive and sophisticated equipment like High-Performance Liquid Chromatography (HPLC) or Gas Chromatography-Mass Spectrometry (GC/MS). This paper proposes a low cost and convenient approach in furan contents estimation based on UV-Vis spectrometry and Fuzzy Logic Theory.
Keywords
fuzzy logic; paper; power transformer testing; transformer oil; Furan derivatives; cellulosic insulating paper; fuzzy logic; solid dielectric degradation; transformer oil; ultraviolet-to-visible spectrometry; Aging; Degradation; Fuzzy logic; IEC standards; Measurement standards; Oil insulation; Petroleum; Power transformer insulation; Power transformers; Spectroscopy; Furans; Furfural; Fuzzy Logic; UV-Vis Spectral Response;
fLanguage
English
Publisher
ieee
Conference_Titel
Electrical and Computer Engineering, 2008. ICECE 2008. International Conference on
Conference_Location
Dhaka
Print_ISBN
978-1-4244-2014-8
Electronic_ISBN
978-1-4244-2015-5
Type
conf
DOI
10.1109/ICECE.2008.4769302
Filename
4769302
Link To Document