High-voltage field testing of GIS from a physical view-point
Author :
Haller, R. ; Hauschild, W. ; Mosch, W.
Author_Institution :
VEB TuR Dresden, West Germany
Abstract :
GIS (gas-insulated substation) field tests are recommended. For GIS of lower rated voltage (<245 kV), where mainly free-moving particles are dangerous, an AC voltage test including sensitive PD (partial discharge) measurement is shown to be efficient. The PD measurement can be replaced by an OLI (oscillating lightning impulse) test. For GIS of higher rated voltage (>245 kV), where fixed defects are mainly dangerous, an AC voltage conditioning and an OLI test are shown to be efficient
Keywords :
electric breakdown of gases; gaseous insulation; high-voltage techniques; insulation testing; partial discharges; substations; 245 kV; AC voltage conditioning; AC voltage test; GIS field tests; HV field testing; failure mechanism; fixed defects; free-moving particles; gas-insulated substation; oscillating lightning impulse; partial discharge measurement; Breakdown voltage; Electrodes; Failure analysis; Flashover; Geographic Information Systems; Glow discharges; Insulation; Partial discharges; Stochastic processes; Testing;