DocumentCode
2557105
Title
ENEL´s experience with on line partial discharge measurement on stator windings of large synchronous hydro generators
Author
Colombo, Emanuela ; Tontini, G.
Author_Institution
ENEL-Centro di Ricerca Elettrica, Milano, Italy
fYear
1990
fDate
3-6 Jun 1990
Firstpage
120
Lastpage
128
Abstract
Results of work in progress at ENEL concerning online measurement of partial discharges in the stator windings of large synchronous hydro generators are reported. The guidelines of this work are basically in accordance with the technique developed by the Ontario Hydro Research Division. Capacitive couplers were set up and permanently installed on the stator windings and/or on the busbars of some 15 hydro generators rated in the range of 50-200 MVA. The main characteristics of these couplers are given, and the basic criteria followed for their installation are briefly reviewed. Pulse waveshapes recorded during operation of the generators are shown, and signals coming from couplers located at different points are compared. Attention is also given to signals resulting from coupling systems installed both inside a generator and along the busbars. Examples of results of online partial discharge measurements performed using a commercially available analyzer are provided
Keywords
hydroelectric generators; partial discharges; stators; synchronous generators; 50 to 200 MVA; ENEL; busbars; capacitive couplers; coupling systems; large synchronous hydro generators; on line partial discharge measurement; stator windings; Couplers; Guidelines; Partial discharge measurement; Partial discharges; Performance analysis; Performance evaluation; Pulse generation; Signal generators; Stator windings; Synchronous generators;
fLanguage
English
Publisher
ieee
Conference_Titel
Electrical Insulation, 1990., Conference Record of the 1990 IEEE International Symposium on
Conference_Location
Toronto, Ont.
ISSN
1089-084X
Type
conf
DOI
10.1109/ELINSL.1990.109722
Filename
109722
Link To Document