• DocumentCode
    2557128
  • Title

    PD-fingerprints of some high voltage apparatus

  • Author

    Fuhr, J. ; Haessig, M. ; Fruth, B. ; Kaiser, T.

  • Author_Institution
    Asea Brown Boveri, Baden-Dattwil, Switzerland
  • fYear
    1990
  • fDate
    3-6 Jun 1990
  • Firstpage
    129
  • Lastpage
    132
  • Abstract
    Partial discharge (PD) measurements performed on different high-voltage apparatus using a computer-controlled phase resolving PD analyzer (PRPDA) are described. The PRPDA system records the PD activity of a test object during a given number of cycles of the applied AC voltage or during a fixed time. Some typical results obtained in SF6-insulated systems gas-insulated systems, power transformers, and power generators in offline and in online conditions are presented and discussed. An advantage of the PRPDA measuring system is the possibility of performing a statistical analysis of the PD data
  • Keywords
    computerised instrumentation; gaseous insulation; insulation testing; machine insulation; partial discharges; power transformers; transformer insulation; SF6; SF6-insulated systems; applied AC voltage; computer-controlled phase resolving PD analyzer; gas-insulated systems; high voltage apparatus; partial discharge fingerprints; power generators; power transformers; statistical analysis; High performance computing; Partial discharge measurement; Partial discharges; Performance analysis; Performance evaluation; Phase measurement; Power generation; Power transformers; System testing; Voltage;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Electrical Insulation, 1990., Conference Record of the 1990 IEEE International Symposium on
  • Conference_Location
    Toronto, Ont.
  • ISSN
    1089-084X
  • Type

    conf

  • DOI
    10.1109/ELINSL.1990.109723
  • Filename
    109723