DocumentCode :
2557160
Title :
Partial discharge amplitude distribution of power transformer oils
Author :
Pompili, M. ; Mazzetti, C. ; Schifani, R.
Author_Institution :
Dept. of Electr. Eng., Rome Univ., Italy
fYear :
1990
fDate :
3-6 Jun 1990
Firstpage :
133
Lastpage :
136
Abstract :
The most commonly used criteria for PDIV (partial-discharge inception voltage) determination are examined using three synthetic transformer oils as test fluids. It is shown that the PD amplitude distribution changes both with increasing applied voltage and with test duration. The use of a multichannel analyzer was shown to be most helpful in rendering the PDIV statistically more meaningful. It is noted that both the number and amplitude of PDs are random phenomena the occurrence of which is hard to predict. Close to the breakdown voltage the PD activity increases and its amplitude spectrum approaches a quasi-exponential shape
Keywords :
insulating oils; partial discharges; power transformers; transformer insulation; PDIV; amplitude spectrum; applied voltage; breakdown voltage; multichannel analyzer; partial-discharge inception voltage; power transformer oils; quasi-exponential shape; random phenomena; synthetic transformer oils; Capacitance; Detectors; Electrodes; Needles; Oil insulation; Partial discharges; Petroleum; Power supplies; Power transformers; System testing;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Electrical Insulation, 1990., Conference Record of the 1990 IEEE International Symposium on
Conference_Location :
Toronto, Ont.
ISSN :
1089-084X
Type :
conf
DOI :
10.1109/ELINSL.1990.109724
Filename :
109724
Link To Document :
بازگشت