• DocumentCode
    2557703
  • Title

    A study of fast transients in gas insulated substations

  • Author

    Coventry, P.F. ; Wilson, A.

  • Author_Institution
    Nat. Grid Res. & Dev. Centre, Leatherhead, UK
  • fYear
    1990
  • fDate
    3-6 Jun 1990
  • Firstpage
    236
  • Lastpage
    239
  • Abstract
    Experimental and theoretical techniques are being used to investigate the response of gas-insulated substations (GISs) to fast transients. Sensors were developed to record fast transient waveforms accurately over a wide frequency range. Their performance under fast transient conditions was verified using a D-dot probe with a known response. Good agreement was recorded by instrumentation with a 200-MHz bandwidth. A computer code was developed to enable electrical stresses in a GIS under fast transient conditions to be studied. The program solves Maxwell´s equations in two dimensions using a finite-difference method. The electric field structure around insulating barriers was studied, and initial results are presented
  • Keywords
    finite element analysis; gaseous insulation; substations; transient response; transients; 200 MHz; 200-MHz bandwidth; D-dot probe; GIS; Maxwell´s equations; computer code; electric field structure; electrical stresses; fast transient conditions; fast transient waveform recording; finite-difference method; gas insulated substations; insulating barriers; two dimensions; wide frequency range; Bandwidth; Finite difference methods; Frequency; Gas insulation; Geographic Information Systems; Instruments; Maxwell equations; Probes; Stress; Substations;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Electrical Insulation, 1990., Conference Record of the 1990 IEEE International Symposium on
  • Conference_Location
    Toronto, Ont.
  • ISSN
    1089-084X
  • Type

    conf

  • DOI
    10.1109/ELINSL.1990.109748
  • Filename
    109748