Title : 
A new after laying dielectric test for underground high-voltage extruded cables
         
        
            Author : 
Koevoets, R.C.A.M.
         
        
            Author_Institution : 
N.V. Kema, Arnhem
         
        
        
        
        
        
            Abstract : 
Problems related to the classical DC test and to the way this test is usually carried out in practice are examined. Information is given on alternative after-laying tests, particularly the oscillating wave test, recommended by CIGRE. The oscillating wave test has been applied several times as an after-laying test on long-length 150-kV XLPE (cross-linked polyethylene) cable systems. Although this test method is more complicated and more expensive than the DC test, experiences so far show that it is promising
         
        
            Keywords : 
cable insulation; cable testing; high-voltage techniques; insulation testing; organic insulating materials; polymers; power cables; 150 kV; AC test methods; CIGRE; DC test problems; accessories; after laying dielectric test; breakdown test; classical DC test; installed cable testing; long length 150 kV XLPE cable systems; oscillating wave test; site test; underground high-voltage extruded cables; Breakdown voltage; Cables; Dielectrics; Electric breakdown; Electric variables measurement; IEC standards; Insulation testing; Low voltage; Stress; System testing;
         
        
        
        
            Conference_Titel : 
Electrical Insulation, 1990., Conference Record of the 1990 IEEE International Symposium on
         
        
            Conference_Location : 
Toronto, Ont.
         
        
        
        
            DOI : 
10.1109/ELINSL.1990.109763