  • Abstract
    In the balanced coupler technique for the detection of discharges in rotating machines, it is common practice to omit grounding the coaxial-line shielding near the couplers in order to avoid induced current loops. Recent measurements demonstrate that providing a high-frequency ground to the coaxial shielding at the capacitive couplers reduces the magnitude of the high-frequency signal propagating along the outside shield. The signal coupling between adjacent coaxial cables is thus reduced, providing a higher signal level and a better signal-to-noise ratio at the detector end
  • Keywords
    earthing; hydroelectric generators; machine testing; partial discharges; shielding; stators; SNR improvement; balanced coupler technique; capacitive couplers; coaxial-line shielding; coupler earthing; high-frequency grounding; hydrogenerators; measurements; partial discharges; rotating machines; stator winding; Alternators; Circuits; Coaxial cables; Coaxial components; Couplers; Detectors; Grounding; Hafnium; Partial discharges; Stator cores;