DocumentCode
2562398
Title
The characteristic features of recovery of the breakdown strength of vacuum switching devices after interruption of high currents
Author
Schade, E. ; Dullni, E.
Author_Institution
ABB Corp. Res. Ltd., Baden-Daettwil, Switzerland
Volume
2
fYear
2000
fDate
2000
Firstpage
367
Abstract
The relevant effects determining the recovery period are discussed. Metal vapor and residual charge at early times after current extinction reduce the breakdown strength. Metal droplets play only a secondary role obviously. The drawing of liquid protrusion out of the molten contact surfaces will be a mechanism in case of high field strength at the contact surfaces. The knowledge about the breakdown processes has to be improved, especially concerning the effect of delayed breakdowns
Keywords
circuit-breaking arcs; electric strength; power distribution protection; switchgear testing; vacuum arcs; vacuum interrupters; breakdown processes; breakdown strength; breakdown strength recovery characteristics; current extinction; high currents interruption; metal droplets; metal vapor; molten contact surfaces; recovery period; residual charge; vacuum switching devices; Breakdown voltage; Delay effects; Dielectric breakdown; Electric breakdown; Interrupters; Medium voltage; Plasma temperature; Power generation economics; Temperature dependence; Vacuum breakdown;
fLanguage
English
Publisher
ieee
Conference_Titel
Discharges and Electrical Insulation in Vacuum, 2000. Proceedings. ISDEIV. XIXth International Symposium on
Conference_Location
Xi´an
Print_ISBN
0-7803-5791-4
Type
conf
DOI
10.1109/DEIV.2000.879005
Filename
879005
Link To Document