• DocumentCode
    2562398
  • Title

    The characteristic features of recovery of the breakdown strength of vacuum switching devices after interruption of high currents

  • Author

    Schade, E. ; Dullni, E.

  • Author_Institution
    ABB Corp. Res. Ltd., Baden-Daettwil, Switzerland
  • Volume
    2
  • fYear
    2000
  • fDate
    2000
  • Firstpage
    367
  • Abstract
    The relevant effects determining the recovery period are discussed. Metal vapor and residual charge at early times after current extinction reduce the breakdown strength. Metal droplets play only a secondary role obviously. The drawing of liquid protrusion out of the molten contact surfaces will be a mechanism in case of high field strength at the contact surfaces. The knowledge about the breakdown processes has to be improved, especially concerning the effect of delayed breakdowns
  • Keywords
    circuit-breaking arcs; electric strength; power distribution protection; switchgear testing; vacuum arcs; vacuum interrupters; breakdown processes; breakdown strength; breakdown strength recovery characteristics; current extinction; high currents interruption; metal droplets; metal vapor; molten contact surfaces; recovery period; residual charge; vacuum switching devices; Breakdown voltage; Delay effects; Dielectric breakdown; Electric breakdown; Interrupters; Medium voltage; Plasma temperature; Power generation economics; Temperature dependence; Vacuum breakdown;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Discharges and Electrical Insulation in Vacuum, 2000. Proceedings. ISDEIV. XIXth International Symposium on
  • Conference_Location
    Xi´an
  • Print_ISBN
    0-7803-5791-4
  • Type

    conf

  • DOI
    10.1109/DEIV.2000.879005
  • Filename
    879005