• DocumentCode
    2562811
  • Title

    Post-arc currents of vacuum interrupters with axial magnetic field contacts under high current and voltage stress

  • Author

    Steinke, K. ; Lindmayer, M. ; Weltmann, K.-D.

  • Author_Institution
    Inst. fur Hochspannungstechnik und Elektrische Energieanlagen, Tech. Univ. Braunschweig, Germany
  • Volume
    2
  • fYear
    2000
  • fDate
    2000
  • Firstpage
    475
  • Abstract
    The post-arc current of vacuum interrupter units with bipolar axial magnetic field contacts has been investigated under conditions of high current (40 to 60 kA RMS) and high steepness of the transient recovery voltage (5 and 10 kV/μs). The arcing time and contact distance, respectively, has been changed by varying the moment of contact separation. By comparison with simulations, the measured clear decrease of the post-arc current and charge with decreasing arcing time can be attributed to lower residual ionization. The dependence of the post-arc current on du/dt is explained by the influence of secondary emission
  • Keywords
    circuit-breaking arcs; electrical contacts; magnetic fields; switchgear testing; vacuum arcs; vacuum interrupters; 40 to 60 kA; arcing time; axial magnetic field contacts; contact distance; contact separation; residual ionization; secondary emission; transient recovery voltage; vacuum interrupter post-arc currents; Anodes; Cathodes; Charge measurement; Current measurement; Electrons; Interrupters; Magnetic fields; Plasma density; Stress; Voltage;
  • fLanguage
    English
  • Publisher
    ieee
  • Conference_Titel
    Discharges and Electrical Insulation in Vacuum, 2000. Proceedings. ISDEIV. XIXth International Symposium on
  • Conference_Location
    Xi´an
  • Print_ISBN
    0-7803-5791-4
  • Type

    conf

  • DOI
    10.1109/DEIV.2000.879030
  • Filename
    879030