  • Title

    Visualization of late breakdown in vacuum

  • Author

    Ponthenier, Jean-Luc ; Giraud, Denis ; Schellekens, Hans

  • Author_Institution
    Res. Center, Schneider Electr. A2, Grenoble, France
  • Volume
    2
  • fYear
    2000
  • fDate
    2000
  • Firstpage
    499
  • Abstract
    Experimental observations of late breakdowns in a vacuum circuit breaker were made using an intensified charge coupled device camera, (ICCD). These late restrikes can cause arc reignition and interruption failure. This type of failure is rare and can be initiated by a number of mechanisms. This paper illustrates the method used to observe this furtive phenomenon. Key images of the phenomenon occurring during breakdown initiation are shown
  • Keywords
    CCD image sensors; vacuum arcs; vacuum breakdown; vacuum circuit breakers; arc reignition; intensified charge coupled device camera; interruption failure; late breakdown visualisation; vacuum; vacuum circuit breaker; Breakdown voltage; Charge-coupled image sensors; Circuit breakers; Circuit testing; Dielectrics; Thermal stresses; Transient analysis; Vacuum arcs; Vacuum breakdown; Visualization;