DocumentCode
2563224
Title
Partial-discharge detector for in-service cables and joints under normal network operating conditions
Author
Morin, Richard ; Gonzalez, Antonio ; Christophe, Patrick ; Poirier, Benny
Author_Institution
Hydro-Quebec, Varennes, Que., Canada
fYear
1991
fDate
22-27 Sep 1991
Firstpage
23
Lastpage
28
Abstract
An evaluation of commercially available partial-discharge detectors was undertaken at IREQ to find a safe device for splicers working in manholes on underground 25 kV electrical distribution networks. Laboratory and field tests were conducted to compare different devices from the standpoints of sensitivity, resolution and equipment characteristics. The radio-frequency approach was then adopted as the underlying principles for a new design of PD detector using different types of probe. A second-generation device has been built, calibrated and successfully tested both in the IREQ High-Power Laboratory and on Hydro-Quebec´s 25 kV underground distribution network for measuring PDs on cables and joints under normal network operating conditions
Keywords
cable jointing; cable testing; charge measurement; partial discharges; power cables; underground cables; underground distribution systems; 25 kV; Hydro-Quebec; IREQ; IREQ High-Power Laboratory; cable joints; in-service cables; normal network operating conditions; partial-discharge detector; radio-frequency approach; underground electrical distribution networks; Acoustic measurements; Acoustic testing; Cables; Circuit testing; Detectors; Probes; Radio frequency; Ultrasonic variables measurement; VHF circuits; Voltage;
fLanguage
English
Publisher
ieee
Conference_Titel
Transmission and Distribution Conference, 1991., Proceedings of the 1991 IEEE Power Engineering Society
Conference_Location
Dallas, TX
Print_ISBN
0-7803-0219-2
Type
conf
DOI
10.1109/TDC.1991.169481
Filename
169481
Link To Document