DocumentCode :
2563616
Title :
Evaluation and comparison of unaged and field aged moisture impervious medium voltage cables
Author :
Arnold, T.P. ; Jeter, D.R. ; Mercier, C.D. ; McDonald, D.L.
Author_Institution :
Southwire Co., Carrollton, GA, USA
fYear :
1991
fDate :
22-27 Sep 1991
Firstpage :
151
Lastpage :
154
Abstract :
Electrochemical treeing is known to be a major cause of failures in cross-linked polyethylene cables. One method of preventing treeing is a moisture impervious layer on the cable. The on-core moisture impervious cable design is commercially available and has a large installed base. Much research has been done in the laboratory on the moisture impervious cable but little testing of field-aged cables has been done. The first phase of an ongoing test program of field-aged moisture impervious cables is described. Samples were removed from field service at a US electric utility in order to begin evaluation of field-aged cables. Also tested were new (1990) and unaged (1984) samples of the same construction as a control. AC high voltage breakdown, lightning impulse breakdown and switching impulse breakdown were performed. Also, material analyses were performed for comparison. These tests were begun in order to develop a database to demonstrate the long-term performance of on-core moisture impervious cables. The results from these preliminary tests indicate that on-core moisture impervious cables perform well in the field
Keywords :
ageing; cable sheathing; cable testing; electric breakdown of solids; impulse testing; insulation testing; life testing; organic insulating materials; polymers; power cables; AC high voltage breakdown; US electric utility; cross-linked polyethylene cables; electrochemical treeing; field aged moisture impervious medium voltage cables; lightning impulse breakdown; switching impulse breakdown; unaged cables; Aging; Breakdown voltage; Cables; Dielectric breakdown; Laboratories; Lightning; Moisture; Polyethylene; Power industry; Testing;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Transmission and Distribution Conference, 1991., Proceedings of the 1991 IEEE Power Engineering Society
Conference_Location :
Dallas, TX
Print_ISBN :
0-7803-0219-2
Type :
conf
DOI :
10.1109/TDC.1991.169500
Filename :
169500
Link To Document :