    Results for long term performance tests on polymer insulated cables up to 230 kV

  • Author

    Zimmermann, H. ; Schwarz, M. ; Mathis, W.E.

  • Author_Institution
    Brugg Cable Ltd., Switzerland
  • fYear
    1991
  • fDate
    22-27 Sep 1991
  • Firstpage
    176
  • Lastpage
    179
  • Abstract
    Accelerated cable life testing is of great importance for polymer insulation to estimate expected cable life under operating conditions. The status of long term performance tests on HV polymer insulated cables with maximum field strength of 15 kV/mm is reported. Some 60 and 110 kV cables have been subjected to cyclic loading with more than two times nominal voltage for seven years. Extrapolation from results after three years accelerated aging indicates a cable life far above the expected 40 years
  • Keywords
    cable insulation; insulation testing; life testing; organic insulating materials; polymers; power cables; 60 to 230 kV; accelerated cable life testing; cyclic loading; long term performance tests; polymer insulated cables; Cable insulation; Cables; Conductors; Electric breakdown; Life estimation; Life testing; Paramagnetic resonance; Plastic insulation; Polymers; Voltage;