Title :
Thermal stress on ZnO surge arresters in polluted conditions. II. Field test results
Author :
Vitet, S. ; Schei, A. ; Stenström, L. ; Lundquist, J.
Author_Institution :
Electricite de France, Clamart, France
Abstract :
For pt.I, see ibid., pp.432-442. The thermal performance of ZnO surge arresters in polluted conditions was studied in the laboratory and in the field. The results from field tests in areas of marine and industrial pollution are presented. A comparison of laboratory and field test results is made on the basis of varistor temperature rise and accumulated charge of external leakage currents
Keywords :
surge protection; testing; zinc compounds; ZnO surge arresters; accumulated charge; external leakage currents; field tests; industrial pollution; marine pollution; polluted conditions; thermal performance; varistor temperature rise; Arresters; Environmentally friendly manufacturing techniques; Industrial pollution; Laboratories; Surges; Testing; Thermal pollution; Thermal stresses; Varistors; Zinc oxide;
Conference_Titel :
Transmission and Distribution Conference, 1991., Proceedings of the 1991 IEEE Power Engineering Society
Conference_Location :
Dallas, TX
Print_ISBN :
0-7803-0219-2
DOI :
10.1109/TDC.1991.169543