DocumentCode
2564439
Title
Application of fault location system in power substations
Author
Mukaiyama, Y. ; Mizuno, K. ; Horide, A. ; Sakakibara, T. ; Maruyama, S. ; Kamata, I. ; Shinoda, A.
Author_Institution
Chubu Electric Power Co., Nagoya, Japan
fYear
1991
fDate
22-27 Sep 1991
Firstpage
459
Lastpage
466
Abstract
To develop a GIS fault location system, a series of development tests were carried out, including arc tests, using actual apparatus. As a result, a system was developed, using pressure wave, gas pressure, optical, vibration, and grounding wire current sensors. These sensors were applied according to the features of equipment structures. While studying important factors in applying fault location sensors, the system was developed while paying particular attention to methods for detecting circuit breaker faults in resistance-grounded substations
Keywords
circuit breakers; fault location; substations; GIS; arc tests; circuit breaker faults; development tests; fault location system; gas pressure sensors; grounding wire current sensors; optical sensors; pressure wave sensors; resistance-grounded substations; vibration sensors; Fault location; Gas detectors; Geographic Information Systems; Grounding; Optical sensors; Sensor phenomena and characterization; Sensor systems; Substations; System testing; Wire;
fLanguage
English
Publisher
ieee
Conference_Titel
Transmission and Distribution Conference, 1991., Proceedings of the 1991 IEEE Power Engineering Society
Conference_Location
Dallas, TX
Print_ISBN
0-7803-0219-2
Type
conf
DOI
10.1109/TDC.1991.169545
Filename
169545
Link To Document