    Recent years have witnessed a relatively large number of power transformers and shunt reactors failures, which were attributed to the presence of corrosive sulfur compounds in the insulating oils and their attending reactions with copper to form electrically conductive copper sulphides. The associated problems appeared to be initially resolved by the addition to the insulating oil small amounts of a metal deactivator, a derivative of 1, 2, 3 benzotriazole (BTA). However, over the past four years additional problems, arose that were principally associated with the evolution of gases from the electrical insulating oils. These observations, recorded in the field as well as reproduced in laboratories, are examined in this paper.
  • Keywords
    corrosion; insulating oils; power transformer protection; corrosion; insulating oils; power transformer failure; shunt reactors failure; Copper; Dielectrics and electrical insulation; Gas insulation; Gases; Inductors; Oil insulation; Petroleum; Power transformer insulation; Power transformers; Shunt (electrical);