    Five different methods for predicting foul weather electromagnetic interference from power overhead lines have been studied. Differences between the predictions in excess of 10 dB are common. Each method has been optimized by adding a constant chosen to minimize the difference between predictions and a set of long term measurements. The rationale for doing this is that each generation function was developed under somewhat different weather conditions. The best optimized method is the one with the smallest difference. The best methods have respectively 1.7 and 4.4 dB RMS differences between average stable foul and average fair weather measurements
  • Keywords
    electromagnetic interference; power overhead lines; EMI; calibration; electromagnetic interference; foul weather; generation function; power overhead lines; Conductors; Electromagnetic interference; Electromagnetic measurements; Equations; Frequency; Magnetic field measurement; Optimization methods; Rain; Testing; Weather forecasting;