    Revenue metering error caused by induced voltage from adjacent transmission lines

  • Author

    Hughes, M. Brent

  • Author_Institution
    Powertech Labs. Inc., Surrey, BC, Canada
  • fYear
    1991
  • fDate
    22-27 Sep 1991
  • Firstpage
    925
  • Lastpage
    929
  • Abstract
    A large zero sequence voltage was found to have been induced onto a 138 kV line from adjacent 500 kV lines where these share the same transmission right-of-way. This zero sequence voltage distorted the 2.5-element revenue metering schemes used for two large industrial customers supplied directly from the affected 138 kV line. As a result, these two customers were overcharged, on average, approximately 3.5% for 15 years. The work done to trace the origins of the zero sequence voltage and quantify the metering error is described. Customer refunds which, in the end, totalled $4 million are calculated
  • Keywords
    errors; metering; power transmission lines; 138 kV; 2.5-element revenue metering schemes; 500 kV; adjacent transmission lines; induced voltage; metering error; zero sequence voltage; Capacitors; Circuits; EMTP; Electrical equipment industry; Electromagnetic modeling; Power transmission lines; Substations; Transformers; Transmission lines; Voltage;