DocumentCode
2568342
Title
Hydrogen sulfide and sulfur dioxide evolution from a valve-regulated lead-acid battery
Author
Robinson, R.S. ; Tarascon, J.M. ; O´Sullivan, T.
Author_Institution
Bellcore, Red Bank, NJ, USA
Volume
1
fYear
1993
fDate
27-30 Sep 1993
Firstpage
440
Abstract
Two incidents concerning copper contamination associated with uninterruptible power systems (UPS) were observed. Valve regulated lead-acid (VRLA) batteries used in the UPSs for back-up powering were diagnosed as the possible source of the contamination. One of the VRLA batteries from the damaged UPS unit was subjected to overcharge in the laboratory, to simulate the incident. Overcharge currents greater than 10 amperes, coupled with battery temperatures over 60°C, can cause a VRLA battery to release significant amounts of hydrogen sulfide and sulfur dioxide. Under extreme conditions, hazardous levels of hydrogen sulfide could be generated. The authors conclude that the contamination was due to copper sulfide, Cu2S, and copper oxide, Cu2 O, formed on copper surfaces as a consequence of hydrogen sulfide evolution and the high humidity inside the UPS enclosure resulting from battery venting
Keywords
copper compounds; hydrogen compounds; lead; secondary cells; sulphur compounds; uninterruptible power supplies; Cu2O; Cu2S; H2S; Pb; Pb-acid battery; SO2; UPS; back-up power; battery venting; copper contamination; copper oxide; copper sulfide; copper surfaces; high humidity; hydrogen sulfide evolution; overcharge currents; sulfur dioxide evolution; uninterruptible power systems; valve-regulated lead-acid battery; Batteries; Contamination; Copper; Gold; Hydrogen; Laboratories; Lead compounds; Pollution; Uninterruptible power systems; Valves;
fLanguage
English
Publisher
ieee
Conference_Titel
Telecommunications Energy Conference, INTELEC '93. 15th International
Conference_Location
Paris
Print_ISBN
0-7803-1842-0
Type
conf
DOI
10.1109/INTLEC.1993.388485
Filename
388485