DocumentCode :
2569517
Title :
Passive temperature regulation of outdoor cabinets and shelters using pure water and night sky radiation
Author :
Baer, Stephen C.
Author_Institution :
ZOMEWORKS CORP., Albuquerque, NM, USA
Volume :
2
fYear :
1993
fDate :
27-30 Sep 1993
Firstpage :
319
Abstract :
Passive air conditioning of outdoor cabinets and shelters has been performed for many years. Heat from the equipment is stored in a thermal mass as latent heat then disposed of through a heat exchanger to the relatively cool night air. During the hottest time of the year, sky temperature is often at least 15°C below ambient, allowing 60 watts/M2 to radiate outward even after the radiator has cooled to ambient temperature. To explore night sky radiation the radiator is larger than the shelter roof, giving both day time shade and extra night cooling. The water is its own thermostat because it ceases to flow by convection to the radiator at 4°C, the temperature of maximum density. Water´s high (80 cal/gram) heat of fusion makes it the perfect medium for storing heat to prevent cabinets from cooling below 0°C. All components must be freeze tolerant
Keywords :
heat exchangers; latent heat; temperature control; thermal energy storage; heat exchanger; heat of fusion; heat storage; latent heat; night sky radiation; outdoor cabinets; outdoor shelters; passive air conditioning; passive temperature regulation; pure water; sky temperature; thermal mass; Batteries; Cooling; Educational institutions; Heat engines; Libraries; Springs; Temperature; Testing; Thermostats; Water storage;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Telecommunications Energy Conference, INTELEC '93. 15th International
Conference_Location :
Paris
Print_ISBN :
0-7803-1842-0
Type :
conf
DOI :
10.1109/INTLEC.1993.388553
Filename :
388553