Title : 
Transformer winding selection associated with reconfiguration of existing double circuit line to six-phase operation
         
        
            Author : 
Stewart, James R. ; Oppel, Laurie J. ; Thomann, Gary C. ; Dorazio, Thomas F. ; Rebbapragada, R.V.
         
        
            Author_Institution : 
Power Technologies Inc., Schenectady, NY, USA
         
        
        
        
        
        
            Abstract : 
Conversion of an existing double circuit three-phase 115 kV overhead transmission line near Binghamton, New York to six-phase operation will provide a commercial demonstration of the feasibility of high phase order power transmission. An important part of this demonstration is specification of the phase/voltage conversion transformers and requirements to permit single pole switching of the line in a practical manner at minimum cost. The results of engineering studies which led to selection of two delta-wye three-phase transformers at each end, one of each pair with reversed polarity to obtain the 60° shift between phases, are presented
         
        
            Keywords : 
power overhead lines; power transformers; transformer windings; 115 kV; 6-phase power transmission lines; Binghamton; New York; delta-wye 3-phase transformers; double circuit 3-phase lines; overhead transmission line; phase/voltage conversion transformers; single pole switching; Coupling circuits; Distributed parameter circuits; Power transmission; Power transmission lines; Rectifiers; Relays; Switches; Switching circuits; Testing; Windings;
         
        
        
        
            Conference_Titel : 
Transmission and Distribution Conference, 1991., Proceedings of the 1991 IEEE Power Engineering Society
         
        
            Conference_Location : 
Dallas, TX
         
        
            Print_ISBN : 
0-7803-0219-2
         
        
        
            DOI : 
10.1109/TDC.1991.169625