DocumentCode
2572860
Title
Analysing a 400 kV power system for an expert system switching
Author
Cipcigan, L. ; Smith, K.S. ; Hiley, J.
Author_Institution
Tech. Univ. Cluj-Napoca, Romania
Volume
3
fYear
2000
fDate
29-31 May 2000
Firstpage
999
Abstract
This paper analyses the switching regime of an important part of the 400 kV Romanian Power System, by means of transient simulations. It defines the best point on wave for the switching operations for a shunt reactor for reactive power/voltage control in a distribution substation. The main purpose of the study is to determine the over-voltages generated in the system when a complex 400 kV subsystem is energized and de-energized. It was assumed that the measurement points were situated at the source side, the shunt reactor side, the overhead lines and the load side. This paper proposes a switching strategy to minimize bus voltage variations and the number of shunt reactor commutations.
Keywords
EMTP; expert systems; overvoltage; power system control; power system simulation; power system transients; reactive power control; reactors (electric); substations; switching; voltage control; 400 kV; EMTP/PSCAD simulation; Romanian Power System; bus voltage variations minimisation; distribution substation; expert system switching; load side; over-voltages; overhead lines; power system; reactive power control; shunt reactor; shunt reactor commutations; shunt reactor side; source side; subsystem de-energization; subsystem energization; switching operations; switching strategy; synchronised switching; transient simulations; voltage control; Analytical models; Expert systems; Inductors; Power system analysis computing; Power system simulation; Power system transients; Reactive power control; Shunt (electrical); Transient analysis; Voltage control;
fLanguage
English
Publisher
ieee
Conference_Titel
Electrotechnical Conference, 2000. MELECON 2000. 10th Mediterranean
Print_ISBN
0-7803-6290-X
Type
conf
DOI
10.1109/MELCON.2000.879702
Filename
879702
Link To Document