DocumentCode
2575352
Title
Evaluation of timing characteristics of a prototype system based on PROFINET IO RT_Class 3
Author
Ferrari, Paolo ; Flammini, Alessandra ; Marioli, Daniele ; Taroni, Andrea ; Venturini, Francesco
Author_Institution
Univ. of Brescia, Brescia
fYear
2007
fDate
25-28 Sept. 2007
Firstpage
1254
Lastpage
1261
Abstract
The PROFINET architecture can provide real-time, high-performance, isochronous communication regardless the presence of other real-time data exchange and TCP/IP traffic for a considerable portion of network bandwidth. In this work some experimental tests have been executed in order to evaluate timing performance of a PROFINET ASIC (ERTEC 400 chip) and its related development kits. Results shows that communication isochrony has been ensured with a jitter of about 100 ns despite TCP traffic (70% of bandwidth) and presence of PROFINET IO RTjClass 1 nodes. On the contrary, some improvements are still needed as regard features of the software stack and of the interface with the application layerl. The highlighted problems will be probably fixed in the next firmware releases planned by manufacturer.
Keywords
IP networks; application specific integrated circuits; field buses; firmware; local area networks; microprocessor chips; real-time systems; synchronisation; telecommunication traffic; transport protocols; ERTEC 400 chip; PROFINET ASIC architecture; TCP/IP traffic; firmware release; real-time Ethernet protocol; real-time data exchange; software stack; timing performance evaluation; Application software; Application specific integrated circuits; Bandwidth; Jitter; Microprogramming; Prototypes; TCPIP; Telecommunication traffic; Testing; Timing;
fLanguage
English
Publisher
ieee
Conference_Titel
Emerging Technologies and Factory Automation, 2007. ETFA. IEEE Conference on
Conference_Location
Patras
Print_ISBN
978-1-4244-0825-2
Electronic_ISBN
978-1-4244-0826-9
Type
conf
DOI
10.1109/EFTA.2007.4416925