DocumentCode :
2584483
Title :
Arc Flash Mitigation Through Use Of Voltage Controlled/Voltage Restrained Overcurrent Elements
Author :
Beach, David ; Johnson, Gerald
fYear :
2007
fDate :
27-29 March 2007
Firstpage :
194
Lastpage :
217
Abstract :
This paper explores voltage controlled overcurrent and voltage controlled ground overcurrent elements which provides a means of allowing pickup currents to be set much lower than in conventional time coordinated overcurrent without loss of coordination. These systems will have circuit breaker based switchgear, overcurrent relaying at each breaker and may have other protection, although most are limited to overcurrent protection. Compared to a system using only inverse time overcurrent, use of voltage controlled overcurrent elements reduces the PPE (personal protective equipment) requirements around the switchgear in the system modeled
Keywords :
arcs (electric); circuit breakers; earthing; overcurrent protection; relay protection; voltage control; PPE; arc flash mitigation; circuit breaker; grounding; overcurrent relaying; personal protective equipment; pickup current; switchgear; voltage controlled-voltage restrained overcurrent protection; Circuit breakers; Electrical equipment industry; Hazards; Medium voltage; Protection; Protective relaying; Switchgear; Transformers; Voltage control; Wiring;
fLanguage :
English
Publisher :
ieee
Conference_Titel :
Protective Relay Engineers, 2007. 60th Annual Conference for
Conference_Location :
College Station, TX
Print_ISBN :
1-4244-0994-2
Electronic_ISBN :
1-4244-0995-0
Type :
conf
DOI :
10.1109/CPRE.2007.359901
Filename :
4201096
Link To Document :
بازگشت