Abstract :
To improve the conventional frequency and tie-line power regulation, a tie-line bias control (TBC) based control scheme is presented in this paper. An additional control loop is set to the conventional TBC control loop to satisfy the MWh constraint and also to satisfy the regulation margin. By the additional control loop, the MWh through the tie-line is kept to its contract MWh not to violate the contract for power accommodation, and the required capacity for the LFC is always maintained to a certain extent even after having quite large load increase. In addition, the required fuel cost for the load-frequency regulation is evaluated.
Keywords :
frequency control; load regulation; power control; power system control; MWh constraint; additional control loop; large load increase; load frequency control; load-frequency regulation; regulation margin; required fuel cost; tie-line bias control; tie-line power regulation; Contracts; Costs; Frequency control; Load flow; Power generation; Power generation economics; Power system economics; Power system simulation; Power transmission lines; Senior members;