DocumentCode
2585671
Title
FRA diagnosis method: simulation applied to feasibility study and efficiency improvement
Author
Moreau, Olivier ; Guillot, Y.
Author_Institution
Direction des Etudes et Recherches, Electr. de France, Clamart, France
Volume
2
fYear
1999
fDate
31 Jan-4 Feb 1999
Firstpage
1059
Abstract
FRA (frequency response analysis) diagnosis method is based on the principle that mechanical winding displacements modify the transformer frequency signature. Intrinsically, the measurement interpretation is rather difficult especially since it requires a reference state which may unfortunately not be available for every transformer. To prove its feasibility, the FRA method, applied to a shell form power transformer, has been simulated by using the software SUMER. SUMER has been developed at the R&D division of Electricite de France (EDF) to derive high frequency transformer models. As simulation results, several types of mechanical defaults can, as a matter of fact, be identified and evaluated thanks to the transfer function modifications. In addition, SUMER modelling makes possible on one hand a better post-processing of the FRA experimental data, and on the other hand optimisation of the measurement procedure.
Keywords
frequency response; power engineering computing; power transformers; transfer functions; transformer windings; EM transient analysis; Electricite de France; SUMER software; efficiency improvement; frequency response analysis diagnosis method; high frequency transformer models; measurement interpretation; mechanical defaults; mechanical winding displacements; shell form power transformer; transfer function modifications; transformer frequency signature; Admittance; Coils; Frequency; Inductance; Leak detection; US Department of Transportation;
fLanguage
English
Publisher
ieee
Conference_Titel
Power Engineering Society 1999 Winter Meeting, IEEE
Print_ISBN
0-7803-4893-1
Type
conf
DOI
10.1109/PESW.1999.747348
Filename
747348
Link To Document